ZA Series · Product view
HIGH-VOLTAGE STORAGE · 30 / 50 kW
ZA Series
Three-Phase Hybrid Inverter
Make larger solar arrays and high-voltage storage work as one three-phase system. Choose 30 or 50 kW output, connect up to 65 kW of PV, and expand with matching inverters when your site needs more capacity.
230 / 400 V three phase · 200–900 V battery · IP66
Select a model to see its ratings below.
THREE-PHASE POWER + HIGH-VOLTAGE STORAGE
A larger system.
Built around high voltage.
ZA brings 30 or 50 kW of conversion capacity to a 230/400 V three-phase system. Pair it with a 200–900 V battery bank and coordinate the system through CAN or RS485 BMS communication.
30 / 50 kW
Rated inverter output
200–900 V
DC battery input
AC OUTPUT
230 / 400 V
230 V phase-to-neutral; 400 V phase-to-phase.
ZA50KW
200 A passthrough
A high-current AC path for the 50 kW model, separate from its inverter conversion rating.
SYSTEM OVERVIEW
Where the power goes
Use solar to supply three-phase site loads and charge high-voltage storage. Bring in AC support when it is needed.
ZA SERIES
Store energy for later. Charge your battery when power is available, then draw on it during battery-powered operation.
Size the complete system. Match inverter output, high-voltage battery capability and the loads that run together.
MULTIPLE SOLAR INPUTS
Give each part of the array its own tracker
Three independent MPPTs on ZA30KW. Four on ZA50KW. Organize the solar array across separate trackers, each with two string connections and a 36 A input limit.
48 kW
Maximum PV input
MPPT 01
36 A
2 PV strings
MPPT 02
36 A
2 PV strings
MPPT 03
36 A
2 PV strings
350–900 V DC MPPT range · 300–1000 V DC input range
65 kW
Maximum PV input
MPPT 01
36 A
2 PV strings
MPPT 02
36 A
2 PV strings
MPPT 03
36 A
2 PV strings
MPPT 04
36 A
2 PV strings
350–900 V DC MPPT range · 300–1000 V DC input range
PARALLEL EXPANSION
Scale with a shared high-voltage battery
Connect up to four matching ZA inverters in a parallel system with a common battery. Coordinate PV capacity, battery current and site demand as the system grows.
Unit 1
Unit 2
Unit 3
Unit 4
Up to 4 matching inverters · Common 200–900 V battery bank
MONITORING + INTEGRATION
Stay connected to the system
ENCLOSURE
IP66
Dust and water-jet protection for the inverter enclosure.
INCLUDED
Built-in WiFi
Check system operation remotely and use CAN / RS485 for battery communication.
OPTIONAL
SNMP / MODBUS
Add network or automation integration through the intelligent slot.
THE DETAILS, SIDE BY SIDE
Technical specifications
Compare 2 configurations by output, solar input and battery system.
Scroll sideways to compare all models.
| Specification | ZA30KW | ZA50KW |
|---|---|---|
| Output | ||
| Rated output power | 30000 W | 50000 W |
| AC phase | Three phase | Three phase |
| Nominal output voltage | 230 V AC phase–neutral / 400 V AC phase–phase | 230 V AC phase–neutral / 400 V AC phase–phase |
| Nominal grid output current | 43.5 A per phase | 72.5 A per phase |
| Grid output voltage range | 184–265 V AC per phase | 184–265 V AC per phase |
| Grid frequency range | 47.5–51.5 Hz or 59.3–60.5 Hz | 47.5–51.5 Hz or 59.3–60.5 Hz |
| Output waveform | Pure sine wave | Pure sine wave |
| Power factor range | 0.9 leading to 0.9 lagging | 0.9 leading to 0.9 lagging |
| Maximum DC/AC efficiency | 96.5% | 96.5% |
| Battery-mode DC/AC efficiency | 97% | 97% |
| Solar input | ||
| Maximum PV input power | 48000 W | 65000 W |
| MPPT trackers | 3 | 4 |
| Maximum input current per MPPT | 36 A | 36 A |
| Strings per MPPT | 2 | 2 |
| Nominal PV voltage | 720 V DC | 720 V DC |
| PV input voltage range | 300–1000 V DC | 300–1000 V DC |
| MPPT voltage range | 350–900 V DC | 350–900 V DC |
| Start-up / initial feeding voltage | 300 / 350 V DC | 300 / 350 V DC |
| Battery & charging | ||
| Battery voltage range | 200–900 V DC | 200–900 V DC |
| Maximum charging power | 30000 W | 50000 W |
| Maximum charge / discharge current | 50 A | 100 A |
| Battery communication | CAN / RS485 BMS | CAN / RS485 BMS |
| AC input | ||
| AC sources | Two independent sources with automatic switching | Two independent sources with automatic switching |
| AC start-up / auto-restart voltage | 120–140 / 180 V AC per phase | 120–140 / 180 V AC per phase |
| Input voltage range | 170–280 V AC per phase | 170–280 V AC per phase |
| Maximum AC input current | 47.9 A | 79.8 A |
| 200 A AC passthrough | — | Available on ZA50KW |
| Control & expansion | ||
| Power priorities | Programmable PV / battery / grid priorities | Programmable PV / battery / grid priorities |
| Parallel operation | Up to 4 units with a common battery | Up to 4 units with a common battery |
| Remote monitoring | Built-in WiFi | Built-in WiFi |
| Communication | RS232 / USB / dry contact / RS485 / CAN / WiFi | RS232 / USB / dry contact / RS485 / CAN / WiFi |
| Intelligent slot | Optional SNMP or MODBUS | Optional SNMP or MODBUS |
| Installation | ||
| Ingress protection | IP66 | IP66 |
| Dimensions (D × W × H) | 290 × 580 × 900 mm | 290 × 580 × 900 mm |
| Net weight | 85 kg | 90 kg |
| Operating temperature | −20°C to +60°C; derating above +45°C | −20°C to +60°C; derating above +45°C |
| Operating humidity | 0–100% RH (non-condensing) | 0–100% RH (non-condensing) |
BEFORE YOU CHOOSE
A few useful answers.
What battery system does ZA use?
ZA connects to a high-voltage battery system within 200–900 V DC, with compatible CAN or RS485 BMS communication. A single 48 V or 51.2 V battery is not a direct match for ZA’s battery input.
How do the two ZA models differ?
ZA30KW provides 30 kW output with three MPPT trackers and up to 48 kW PV input. ZA50KW provides 50 kW output with four trackers and up to 65 kW PV input. Each tracker accepts up to 36 A and two PV strings.
Which model provides 200 A AC passthrough?
The 200 A passthrough feature belongs to ZA50KW. Passthrough current describes the AC path through the unit; it does not increase the inverter’s 50 kW rated conversion output.
Can multiple ZA units share one battery system?
Yes. ZA supports up to four units in a parallel system with a common battery. Size the high-voltage battery bank, BMS, switchgear and connected loads together.
Is remote monitoring included?
Built-in WiFi supports remote monitoring. CAN and RS485 provide battery communication, while RS232, USB and dry contact support integration. SNMP or MODBUS through the intelligent slot is optional.